国产亚洲自拍成人_久久亚洲精品三级_欧美成人午夜精品免费福利_狂野欧美成人亚洲精品_精品视频xxxxx资源色资源网_亚洲第八十七页亚洲九十七页_潮喷流白浆无码色网视频_69成人国产精品视频免费_国产精品柳州莫菁69影院_在线观看中文字幕你懂得

Where are you now:Home / Products / Static relay

Static relay

80 series voltage relay
  • 80 series voltage relay
  • 80 series voltage relay
  • 80 series voltage relay
  • 80 series voltage relay
  • 80 series voltage relay
  • 80 series voltage relay
80 series voltage relay

1. Application

Over-voltage relays are used to determine the over-voltage of power equipment such as generators, transformers and transmission lines, and are used as over-voltage protection.

Low-voltage relays are used to judge that the voltage of power equipment such as generators, transformers and transmission lines is too low, used as power loss protection or as a blocking element.

It can completely solve the defects of contact jitter and refusal to move when the electromagnetic relay is running, the fixed value setting accuracy is not high, and the return coefficient is affected by the residual magnetism. It can replace the electromagnetic relay of DY-31\32C\35\36C.


2. Model definition


20140111210295149514 (1).jpg


3. Working principle and main performance

3.1 Working principle:

The AC voltage is converted by the converter to the AC voltage required by the series of relays; then the harmonics other than 50HZ are filtered through the 50HZ bandpass; then the DC voltage is sent to the setting circuit through rectification and filtering; the setting circuit depends on changing the amplifier of the operational amplifier Multiplier to change the setting value; the output voltage UZ of the setting loop is compared with the threshold voltage UB through the level detector; then the output of the relay J is driven to act.

3.2 The action process of low voltage and over voltage relay:

3.2.1 For the overvoltage relay in normal operation, UZ<UB, relay J does not act, the moving contacts 1-3, 7-19 are disconnected, and the moving disconnect contacts 3-17, 5-7 are closed; In the case of UZ≥UB, the relay J acts, the moving contacts 1-3 and 7-19 are closed, and the moving breaking contacts 3-17 and 5-7 are disconnected.

3.2.2 For low-voltage relays, under normal operation conditions UZ>UB, relay J does not operate, the moving contacts 1-3 and 7-19 are disconnected, and the moving breaking contacts 3-17 and 5-7 are closed; In the case of failure, UZ≤UB, relay J will act, moving-on contacts 1-3, 7-19 are closed, and moving-breaking contacts 3-17, 5-7 are disconnected.

3.3 The use of high-efficiency integrated circuits and components, with stable performance, high reliability, high accuracy of the action value, small discrete value, wide setting range, fast action and return speed, good return coefficient, small load on the transformer, and vibration resistance , Anti-interference and high insulation level.

3.4 The protection setting value is set by the dial switch on the relay panel, and the setting calculation formula is indicated. The setting is intuitive and convenient, and the debugging is simple and convenient. No adjustment is required on site.

3.5 The product installation structure includes embedded board rear wiring and protruding board front wiring as well as standard 35mm rail type terminal block wiring, which is convenient for on-site installation and has strong versatility.

Contact Us
Shenzhen Renergy Electric Equipment Co., Ltd.
Address: 102 on the fourth and first floors of Building A, Building C, Shangxue Technology Industrial City, Xinxue Community, Bantian Street, Longgang District, Shenzhen
Tel:0755-89325335    84505292
Fax:0755-89325332